NEC Calculation Tool

Voltage Drop Calculator

Reviewed by Ken Pergeson, Permit Expediter & Code Compliance Consultant, Ventura County, CA ·

Enter the circuit and the wire. The calculator uses the DC resistance values in NEC Chapter 9, Table 8 and shows the volts lost, the percentage and the smallest size that stays under your limit.

The Formula

Voltage drop is Ohm's law applied to the wire itself: the current times the resistance of the conductors.

  • Single-phase: VD = 2 × L × R × I ÷ 1,000
  • Three-phase: VD = 1.732 × L × R × I ÷ 1,000

L is the one-way length in feet, I is the load in amps, and R is the resistance in ohms per 1,000 feet from Chapter 9, Table 8 (stranded, uncoated copper or aluminum at 75°C). Percent drop = VD ÷ source voltage × 100. Table 8 is DC resistance, which is accurate for the small and mid-size conductors used on most exams. For large AC feeders, Table 9 effective impedance is more precise.

Worked Example

A 120 V single-phase branch circuit carries 20 A to a load 100 ft away on 12 AWG copper. Table 8 lists 1.98 Ω/kft.

VD = 2 × 100 × 1.98 × 20 ÷ 1,000 = 7.92 V, which is 7.92 ÷ 120 = 6.6%. That is over the 3% recommendation. 10 AWG (1.24 Ω/kft) gives 4.96 V, 4.1%. 8 AWG (0.778) gives 3.11 V, 2.6%, so 8 AWG is the smallest copper size under 3%.

Three-phase check: 480 V, 100 A, 250 ft on 1/0 copper (0.122 Ω/kft). VD = 1.732 × 250 × 0.122 × 100 ÷ 1,000 = 5.28 V, or 1.1%.

Table 8 Resistance Used

SizeCopper Ω/kftAluminum Ω/kft
14 AWG3.145.17
12 AWG1.983.25
10 AWG1.242.04
8 AWG0.7781.28
6 AWG0.4910.808
4 AWG0.3080.508
3 AWG0.2450.403
2 AWG0.1940.319
1 AWG0.1540.253
1/00.1220.201
2/00.09670.159
3/00.07660.126
4/00.06080.100
250 kcmil0.05150.0847
300 kcmil0.04290.0707
350 kcmil0.03670.0605
400 kcmil0.03210.0529
500 kcmil0.02580.0424
600 kcmil0.02140.0353
750 kcmil0.01710.0282
1000 kcmil0.01290.0212

Limits

The calculator checks voltage drop only. A wire that passes on voltage drop must still have enough ampacity under 310.16 and the terminal rules in 110.14(C). It assumes a balanced load and a 75°C conductor; a cooler wire has slightly less resistance and less drop.

Frequently Asked Questions

What is the maximum voltage drop allowed by the NEC?

Informational notes in 210.19 and 215.2 recommend no more than 3% on a branch circuit or feeder and 5% total to the farthest outlet. They are recommendations, not enforceable rules, unless a specific article or your local code makes them mandatory.

Why is the single-phase formula 2 x L?

Current flows out on one conductor and back on the other, so the total wire length is twice the one-way distance. On a balanced three-phase circuit the factor is the square root of 3, about 1.732, instead of 2.

Which K value should I use on an exam?

Many exam prep books use K = 12.9 for copper and 21.2 for aluminum with VD = 2KLI/CM. Using the exact Table 8 resistance, as this calculator does, gives nearly the same answer and is what the code table actually lists.

Sources

Practice code questions on our Journeyman Electrician Practice Test (NEC 2023), or size a device box with the Box Fill Calculator.